FX-PCA2611
-
6 - Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohm, or Binary Dry Contact
-
2 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
-
2 - Analog Outputs: Defined as 0–10 VDC or 4–20 mA
-
3 - Binary Outputs: Defined as 24 VAC Triac (selectable internal or external source power)
-
4 - Configurable Outputs: Defined as 0–10 VDC or 24 VAC Triac BO
FX-PCA Advanced Application Programmable Controller
FX80 Supervisory Controller
-
Fully Commissioned and Licensed Out of the Box
-
Web-Based User Interface
-
Adoption of Industry Standard Communication Protocols
-
Embedded Configuration Tool
-
Modular Design
-
Small, Compact Design
-
graphical system user interface with an HTML5 web profile
-
FX-PCA controllers feature an integral real-time clock and support time-based control logic, such as scheduling, alarming, and trending.
-
The FX-PCAs include RS-485 field bus networking with selectable N2 or BACnet MS/TP protocols.
-
FX-PCAs also support wireless field bus networking and sensing by adding FX-ZFR
accessories. -
Writable flash memory allows standard or customized applications to be downloaded from the FX-PCT and enables persistent application data.
-
Support for the FX-DIS17 remote display for monitoring and commanding of I/O and configuration parameters
FX-PCA2612-1 and FX-PCA2612-2
-
5 - Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohm, or Binary Dry Contact
-
4 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
-
4 - Configurable Outputs: Defined as 0–10 VDC or 24 VAC Triac BO
-
2 - Relay Outputs: (Single-Pole, Double-Throw) Rated as UL 916; 1/4 hp 120 VAC, 1/2 hp 240 VAC; 360 VA Pilot Duty at 120/240 VAC (B300); 3 A Non-inductive 24-240 VAC; EN 60730: 6 (4) N.O. or N.C. only
-
3 - Relay Outputs: (Single-Pole, Single-Throw) Rated as UL 916: 1/4 HP 120 VAC, 1/2 HP 240 VAC; 360 VA Pilot Duty at 120/240 VAC (B300); 3 A Non-inductive 24-240 VAC; EN 60730: 6 (4) N.O. or N.C. only
FX-PCA3611-0A and FX-PCA3611-0
-
8- Universal Inputs: Defined as 0-10 VDC, 4-20 mA, 0-600k ohms, or Binary Dry Contact
-
6 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
-
6 - Binary Outputs: Defined as 24 VAC Triac (external power source only)
-
6 - Analog Outputs: Defined as 0-10 VDC or 4-20 mA
-
FX-PCG Series devices are programmable controllers that can be combined with the FX-PCX Expansion I/O Modules to monitor and control a wide variety of HVAC equipment.
-
The FX-PCGs include RS-485 field bus networking with selectable N2 or BACnet MS/TP protocols.
-
FX-PCGs also support wireless field bus networking and sensing by adding FX-ZFR accessories.
-
Writable flash memory allows standard or customized applications to be downloaded from the FX-PCT and enables persistent application data.
-
FX-PCG controllers feature 32-bit microprocessors, patented continuous tuning adaptive control logic, peer-to-peer communications, and are available with an optional built-in LCD keypad and display.
FX-PCG General Purpose Programmable Controllers
FX-PCG26 Models
-
6 - Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohm, or Binary Dry Contact
-
2 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
-
3 - Binary Outputs: Defined as 24 VAC Triac (selectable internal or external source power)
-
4 - Configurable Outputs: Defined as 0–10 VDC or 24 VAC Triac BO
-
2 - Analog Outputs: Defined as 0–10 VDC or 4–20 mA
FX-PCG16 Models
-
2 - Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohm, or Binary Dry Contact
-
1 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
-
3 - Binary Outputs: Defined as 24 VAC Triac (selectable internal or external source power)
-
4 - Configurable Outputs: Defined as 0–10 VDC or 24 VAC Triac BO
FX-PCX Expansion Input/Output Modules
-
The FX-PCXs are expansion I/O modules with integral RS-485 MS/TP communications
-
FX-PCXs can serve in one of two capacities, depending on where they are installed in the control system.
-
ZigBee® Wireless FC/SA Bus Interface
-
Universal Inputs and Configurable Outputs - Allow multiple signal options per channel to provide input/output flexibility.
-
Ability to reside on the FC Bus or SA Bus provides application flexibility
FX-PCX1711-0
-
4-Point Expansion Input/Output Module with 4 BI, FC and SA Bus Support.
FX-PCX2711-0
-
6-Point Expansion Input/Output Module with 2 UI, 2 UO, 2 BO, FC and SA Bus Support. Relays are rated for 120/240 VAC.
FX-PCX2711-2
-
6-Point Expansion Input/Output Module with 2 UI, 2 UO, 2 BO, FC and SA Bus Support. Relays are rated for 240 VAC.
FX-PCX2721-0
-
10-Point Expansion Input/Output Module with 8 UI, 2 AO, FC and SA Bus Support
FX-PCX3711-0
-
12-Point Expansion Input/Output Module with 4 UI, 4 UO, 4 BO, FC and SA Bus Support. Relays are rated for 120/240 VAC.
FX-PCX3711-2
-
12-Point Expansion Input/Output Module with 4 UI, 4 UO, 4 BO, FC and SA Bus Support. Relays are rated for 240 VAC.
FX-PCX3721-0
-
16-Point Expansion Input/Output Module with 16 BI, FC and SA Bus Support
FX-PCX3731-0
-
16-Point Expansion Input/Output Module with 8 BI, 8 BO, FC and SA Bus Support
FX-PCX4711-0
-
17-Point Expansion Input/Output Module with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, FC and SA Bus Support

-
FX-ZFR Series Wireless Field Bus System uses ZigBee™ technology to provide a wireless platform for Facility Explorer Programmable Controllers
-
The wireless mesh network enhances reliability by providing redundant transmission paths for the data through other routers in the mesh network.
-
The wireless products within a Facility Explorer system are ideal for any location where it is cost-prohibitive, difficult, or aesthetically unappealing to hardwire between Facility Explorer products.
-
The FX-ZFR Series Wireless Field Bus System is approved by national compliance agencies for use only in the United States and Canada.
FX-ZFR Series Wireless Field Bus System