BAC-5831-LNX

  • 16 universal inputs, each of which is programmable as an analog, binary, or accumulator object (accumulators limited to three per controller)

  • 12 universal outputs, each of which is programmable as an analog or binary object

  • Real time clock with power backup for 72 hours

  • Output override boards (HPO-6700 series)

  • Programs and program parameters are stored in nonvolatile memory

  • Automatic restart after power failure

  • MS/TP at up to 76.8 kilobaud (network connections are supervised in smoke control applications)

BAC-7001-LNX and BAC-7051-LNX

  • 3 universal inputs each of which is programmable as an analog, binary or accumulator objects. A fourth input is dedicated to the airflow sensor.

  • 3 universal outputs each of which is programmable as an analog or binary object.

Advanced Application Controller

Advanced Application Controllers
for Variable Air Volume Terminal Units and VAV Fan Induction Units

  • Made in U.S.A

  • BACnet MS/TP compliant

  • Automatically assigns the MAC address and the device instance

BAC-7003-LNX and BAC-7053-LNX

  • 3 universal inputs each of which is programmable as an analog, binary or accumulator objects. A fourth input is dedicated to the airflow sensor.

  • 1 Universal output that is programmable as an analog or binary object

  • 1 Optically isolated triac output, programmable as a binary object

  • 1 normally open relay contact

  • Standard VAV control sequences are incorporated to provide pressure independent control of a single-duct VAV unit.

  • On-board airflow sensor for use with a single or multi-point differential pressure measuring station or pilot tube.

  • Use to control heating, cooling, cooling with heat change-over, cooling with time proportional reheat or three‑stage, sequential reheat.

Simply VAV Controllers

BAC-8001, BAC-8005, BAC-8205 and BAC-8007

  • No special programming skills or software tools are required

  • Automatically detects sensors as they are connected

  • Staged, modulated, floating, or time proportional reheat

  • Series or parallel fan control

  • Single or dual duct application

  • Optically isolated triac output.

  • Actuator position feedback for true damper positioning (BAC-8205 only)